Compressed Gas: Requirements Matrix
Requirements for the safe use of hazardous gas are determined by the hazard class of the gas.
- Determine the hazard class by reviewing the Classification of Hazard chart and the Toxic and Hazardous Gas Classification Chart.
- Submit a Chemical Registration Form via BioRAFT.
- Follow the appropriate requirements below.
Requirements | Class 1 | Class 2 | Class 3 | Class 4 |
---|---|---|---|---|
Exhausted enclosure (gas cabinet or fume hoods) | C1 | x | x | |
Treatment to 1/2 IDLH at atmosphere | x | x | x | |
Leak Check (of installed system) | x | x | x | |
Emergency Response Plan, Team and Drills | x | x | x | |
Flow-limiting device or flow-restricting orifice | C1 | x | x | |
Use in sprinkled spaces | x | x | x | |
Documented annual maintenance | x | x | x | |
Compatible piping | x | x | x | |
Purge system | C1 | x | x | |
Detector system | C2 | C1 | C1 | x |
Emergency alarms (and explanatory signs) | C1 | x | x | |
Welded, compatible piping | x | x | ||
Local shut off | x | x | ||
Interlocks | x | x | ||
Emergency power (alarm, detector, ventilation) | x | x | ||
Monitored secondary containment | C1 | |||
Auto shut – off (manual or detector triggered) | x | x | ||
Exhaust flow alarm | x |
C1 – These requirements are conditional base on process and space allocated and will be determined if required by the Chemical Hygiene Officer and UTD Fire Marshal.
C2 – An oxygen sensor may be required if it is determined that the location where the compressed gas is being used or stored presents a risk of asphyxiation to the users and/or first responders.
Explanation of Requirements
Exhausted enclosure (gas cabinet or fume hoods)
An exhausted enclosure includes gas cabinets and chemical fume hoods.
All Class 4 and 3 gases must be kept in an exhausted enclosure at all times.
Class 2 gases, lecture bottled flammable gases, and oxidizing gases are conditional, depending on the application and the specific gas in question, and will be determined by the Chemical Hygiene Officer.
Fume hood cylinder storage/use requirements
- Be certified annually by Risk & Safety for proper airflow.
- Must be approved by the UTD Chemical Hygiene Officer. Must be properly restrained.
Gas cabinet cylinder storage/use requirements
- Operate at negative pressure in relation to the surrounding area.
- Be provided with self-closing limited access ports or non-combustible windows to give access to equipment controls.
- Average face velocity at the face of the access ports or windows shall not be less than 200 feet per minute (1.01 m/s) with a minimum of 150 feet per minute (0.76 m/s) at any 1 point of the access port or window.
- Connected to an approved exhaust system.
- Equipped with automatic fire sprinkler system protection, and must be constructed and ventilated according to code requirements. Be provided with self-closing doors.
- Be constructed of not less than 0.097 –inch (2.46 mm) (12 gage) steel, must be UL Certified
- Cabinets containing more than three cylinders must be reviewed by Risk & Safety to ensure safe storage.
- Be certified annually by Risk & Safety for proper air flow.
Treatment to 1/2 IDLH at atmosphere
Treatment systems must be designed to reduce the maximum allowable discharge concentration of the gas to 1/2 IDLH (Immediately Dangerous to Life and Health) at the point of discharge to the atmosphere.
When more than 1 gas is emitted to the treatment system, the treatment system must be designed to handle the worst-case release based on the release rate, the quantity, and the IDLH for all the gases stored or used.
Leak Check (of installed system)
Gas systems must be leak tested at the following intervals:
- Upon receipt
- At installation
- Periodically during operation, responsibility of the laboratory
- At disconnect / shipping
It is critical that these gases also be leak tested prior to removal from their exhausted enclosures and subsequent to transport, or if you have reason to believe that the system has been compromised.
Emergency Response Plan, Team, and Drills
All laboratories must have an emergency response plan that addresses the use and/or storage of compressed gases and must be readily available for review by the UTD Chemical Hygiene Officer in the event of an emergency on campus.
Flow-limiting device or flow-restricting orifice
Use a flow-limiting device to restrict hazardous gas flow rates to just over maximum flow required (e.g., flow restricting orifice). These devices must be installed immediately downstream of each gas cylinder. With each connection point, there may be a need for more detection systems, contact the UTD Chemical Hygiene Officer to understand if your set up requires more than one point of detection.
For small scale experiments, such as fume hood use, a needle valve is sufficient.
For large cylinders, a flow restricting orifice must be installed by the gas supplier in the cylinder valve or installed in the gas purge panel.
Use in sprinkled spaces
Sprinkler protection is required in all spaces unless other approved by the UTD Fire Marshall and Chemical Hygiene Officer. If gas is found in an area without a sprinkler system, the Fire Marshal and Chemical Hygiene Officer will lock out/tag out the system and notify the responsible party.
Documented annual maintenance
Keep records of all maintenance associated with gas systems (e.g., gas detection calibration and/ or repairs). The University Gas Detection System receives biannual maintenance and the records are stored within the Risk & Safety Office. If you have questions regarding the maintenance, please contact the Chemical Hygiene Officer. Detection systems that are not on the University Gas Monitoring System must be maintained by the lab and documented in the laboratories files. They must be readily available to give to the Chemical Hygiene Officer in the event the detector system engages or there are issues with the local sensor.
Compatible piping
Piping, tubes, valves, fittings, and related components must be:
- Designed and fabricated from materials compatible with the material to be contained, to check compatibility review the SDS
- Of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subject
- Identified in accordance with nationally recognized standards to indicate the material conveyed
Examples:
- Hydrogen – Use only stainless steel piping and fittings.
- Oxygen – Use steel, brass, copper or stainless steel (as per National Fire Protection Association regulations).
- Arsine, phosphine, ammonia – Use only stainless steel piping and fittings.
See the section on “Welded, compatible piping” below for additional information.
Purge system
The ability to purge the area between the cylinder valve and the regulator with an inert gas prior to maintenance or cylinder change out is required.
Inert gases used for this purpose must be used solely for this purpose and no other operation.
Detector system
A continuous gas-detection system is required to detect the presence of gas at or below the permissible exposure limit or ceiling limit. A few buildings on campus have a monitoring system in place for flammable and toxic gases. Contact the Chemical Hygiene Officer to review if your gas system may be added to the University Gas Detection System.
The detection system must:
- Initiate a local alarm and transmit a signal to a constantly attended control station (exceptions may apply contact the Chemical Hygiene Officer).
- Be capable of monitoring the room or area in which the gas is stored at or below the permissible exposure limit or ceiling limit and the discharge from the treatment system at or below 1/2 IDLH (Immediately Dangerous to Life and Health) limit.
- The alarm must be both inside and outside the storage area. The audible alarm must be distinct from all other alarms.
An oxygen sensor may be required if it is determined that the location where this compressed gas is being used or stored presents a risk of asphyxiation.
Emergency alarms (and explanatory signs)
Alarm system must be posted with information on:
- What the alarm states mean
- What actions to take
- Who to contact
Welded, compatible piping
Piping and tubing must:
- Have welded or brazed connections throughout unless an exhausted enclosure is provided.
- Not be located in any portion of a corridor unless otherwise approved by the UTD Fire Marshal.
See the section on “Compatible piping” above for addition information.
Local shut off
Personnel must be able to shut the system off at the source. Standard Operating Procedures for how to shut off the system, especially after hours, must stored near the gas system in the event of an emergency.
Interlocks
An automatic shut down of gas flow must be initiated when any of these conditions occur:
- Hazardous condition is detected
- Seismic disturbance
- Loss of power – see the “Emergency power” section for more information
- Excess-flow-triggered shut-off – Where gases are carried in pressurized piping above 15 psig (103.4 kPa), excess flow control must be provided
- Loss of vacuum
- Loss of cooling
- Loss of ventilation
Emergency power (alarm, detector, ventilation)
Emergency power must be provided for these systems:
- Exhaust ventilation (including the power supply for treatment systems)
- Gas cabinet ventilation
- Exhausted enclosure ventilation
- Gas-detection
- Emergency alarm
A UPS (Universal Power Supply) is not sufficient as an emergency power supply for these systems.
Monitored secondary containment
Any secondary containment system must have a detection system.
Auto shut – off (manual or detector triggered)
Exhaust flow alarm
Should ventilation become inadequate, an audible and visual alarm must be available.